Draeger PEX 3000 Flammable Gas Detector
The Draeger PEX® 3000 functions as a dependable transmitter that detects flammable gases and vapors before reaching their lower explosive limit of 100 %LEL. The device provides expanded explosion protection to your entire facility infrastructure. This device operates with a catalytic bead sensor that provides reliable long-term measuring signals and instant gas detection.
- Six variants of transmitters
- Simple installation
- One-man Calibration
- Explosion Protection
- Low gas concentrations
- The catalytic bead sensor
- Oil refineries/mining/OnShore/Off Shore /Tank Farms/Water treatment plants
- Continous monitoring of Hydrocarbon , Hydrogen Flammable Gases using Catalytic technology without Display or any indication
- Normal measurment possible with 4-20mA
- Hazardous area Application (zone 1,Zone2)
- Continous monitoring of Hygrogen in battery rooms
| Measuring range |
|
| Power supply | 12 to 30 V d.c. (nominal 24 V d.c.), max. 110 mA at 24 V |
| max. cable length (at 24 V, 250 Ohms) | 2,400 m at 3 x 1.5 mm2, 1,600 m at 3 x 1.0 mm2, 1,200 m at 3 x 0.75 mm2 |
| Signal output |
|
| Response time (at 25 °C, methane) | t50: 3 ... 5 s to t90: 8 ... 10 s |
| Temperature | -40 to +65 °C (see below) |
| Pressure | 700 to 1,300 hPa |
| Humidity | 5 to 95 % r. H. |
| Enclosure material | glass fiber reinforced polyester (GRP) |
| Enclosure protection | IP 66 |
| Dimensions (W x H x D) | ca. 80 x 145 x 55 mm |
| Weight | ca. 600 g (Typ XTR 0090, XTR 0091: ca. 450 g) |
| Expected sensor lifetime | typical > 3 years |
| Performance approval | acc. to EN 60079-29-1 for the a.m. gases and vapours (100 %LEL variants only) |